Appendix, Codes – Lenze ECSCExxx Power supply module User Manual

Page 134

Advertising
background image

Appendix

Codes

12

l

134

EDBCSXE040 EN 7.0

Parameter

C0173

Designation

Mains voltage selection

Data type: INTEGER_32

Index: 24402

dec

= 5F52

hex

Mains voltage selection

^ 67
Selection list

(Lenze setting printed in bold)

Information

No response

0 Operation on 230 V mains

1 Operation on 400 V mains

2 Operation on 460 V mains

3 Operation on 480 V mains

4 Automatic determination

Parameter

C0178

Designation

Elapsed−hour meter

Data type: INTEGER_32

Index: 24397

dec

= 5F4D

hex

Display of the time during which the power supply module was enabled.

Display range

(min. value | unit | max. value)

−214748

h

214748

Parameter

C0179

Designation

Power−on time meter

Data type: INTEGER_32

Index: 24396

dec

= 5F4C

hex

Display of the time during which the DC bus was charged.

Display range

(min. value | unit | max. value)

−214748

h

214748

Parameter

C0183

Designation

Module diagnostics

Data type: INTEGER_32

Index: 24392

dec

= 5F48

hex

l

Display of fault or status information.

l

If several pieces of fault or status information are available at the same time, the information with the lowest
number is displayed.

Display list

Information

0 No fault

101 Initialisation phase

102 TRIP is active

104 Message is active

142 Pulse inhibit (IMP) is active

250 Warning is active

Parameter

C0200

Designation

Firmware identification (ID)

Data type: VISIBLE_STRING

Index: 24375

dec

= 5F37

hex

Display of the firmware identification (ID)

Parameter

C0201

Designation

Firmware creation date

Data type: VISIBLE_STRING

Index: 24374

dec

= 5F36

hex

Display of the firmware creation date

Parameter

C0204

Designation

Device serial number

Data type: INTEGER_32

Index: 24371

dec

= 5F33

hex

Display of the device serial number

Advertising