Configuring system bus (CAN)

Individual addressing

Display of the resulting identifiers

8

l

87

EDBCSXE040 EN 7.0

Save changes with C0003 = 1.

The settings are only accepted after carrying out one of the following actions:

ƒ

Renewed switch−on of the 24 V low−voltage supply

ƒ

Reset node via the bus system (by the network management (NMT))

ƒ

Reset node with C0358 = 1

)

Note!

If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).

Display of the resulting identifiers

C0355 is the display code for the resulting identifiers:

ƒ

General addressing (

^

164):

Identifier (COB−ID) = basic identifier + adjustable node address (node ID)

ƒ

Individual addressing (

^

86):

Identifier (COB−ID) = 384 + ID offset (C0354)

Parameter

C0355

Designation

CAN_IN/OUT identifier (COB−IDs)

Data type: INTEGER_32

Index: 24220

dec

= 5E9C

hex

Display of the CAN_IN/OUT identifiers (COB−IDs)

^ 87
Display range

(min. value | unit | max. value)

0

2047

Subcodes

Information

C0355/1

COB−ID CAN1_IN

C0355/2

COB−ID CAN1_OUT

C0355/3

COB−ID CAN2_IN

C0355/4

COB−ID CAN2_OUT

C0355/5

COB−ID CAN3_IN

C0355/6

COB−ID CAN3_OUT