6 mains chokes, Mains chokes, Appendix – Lenze ECSCExxx Power supply module User Manual

Page 171

Advertising
background image

Appendix

Overview of accessories

12

l

171

EDBCSXE040 EN 7.0

12.4.6

Mains chokes

It is not mandatory to use a mains choke for operating the ECS modules. The respective
application determines whether a mains choke is required or not.

Advantages when using a mains choke:

ƒ

Lower system perturbations
– The waveform of the mains current is approximated to the sinusoidal shape.
– Reduction of the effective mains current by up to 25%.
– Reduction of the mains, cable and fuse load.

ƒ

The effective DC−bus current also decreases by up to 25%.

ƒ

Increased service life of the connected axis modules
– A mains choke reduces the AC current load of the DC−bus capacitors and thus

increases their service life.

ƒ

Low−frequency radio interference voltages are reduced.

Please note:

ƒ

With mains choke operation the maximally possible output voltage does not fully
reach the value of the mains voltage.

ƒ

For operation of drives for accelerating duty with high peak currents, it is
recommended to use mains chokes with linear L/I characteristic (Lenze types
ELN3...).

ƒ

The choke rating is to be checked and adapted to the respective conditions.

Mains chokes for the power supply modules:

Power supply module

type

Mains choke type

I

r

[A]

L

r

[mH]

Short−circuit

voltage (U

k

)

ECSxE012

ELN3−0150H024

3 x 24

3 x 1.5

4 %

ECSxE020

ELN3−0088H035

3 x 35

3 x 0.88

ECSxE040

ELN3−0055H055

3 x 55

3 x 0.55

Advertising