Appendix

General information about the system bus (CAN)
Parameter data transfer

12

l

160

EDBCSXE040 EN 7.0

The command must contain the following information:

Command

4−byte data

(5. ... 8. byte)

2−byte data

(5. and 6. byte)

1−byte data

(5. byte)

Block

hex

dec

hex

dec

hex

dec

hex

dec

Write request

(Transmit parameter to the controller )

23

35

2B

43

2F

47

21

33

Write response

(Acknowledgement, controller
response to write request)

60

96

60

96

60

96

60

96

Read request

(Request to read a controller
parameter)

40

64

40

64

40

64

40

64

Read response

(Response to read request with
current value)

43

67

4B

75

4F

79

41

65

Error response

(The controller reports a
communication error)

80

128

80

128

80

128

80

128

"Error response" command: In case of a communication error an "Error response" is
generated by the addressed node. This telegram always contains the value "6" in Data 4
and an error code in Data 3.

The error codes are standardised acc. to DS301, V4.02.

Addressing by index and subindex

The parameter or Lenze code is addressed with these bytes according to the following
formula:

Index = 24575 − (Lenze code number)

Data 1 ... Data 4

Parameter value length depending on the data format

Parameter value

(Length: 1 byte)

00

00

00

Parameter value (length: 2 bytes)

00

00

Low byte

High byte

Parameter value (length: 4 bytes)

Low word

High word

Low byte

High byte

Low byte

High byte

)

Note!

Lenze parameters are mainly represented as data type FIX32 (32 bit value with
sign, decimally with four decimal positions). To obtain integer values, the
desired parameter value must be multiplied by 10,000

dec

.

The parameters C0135 and C0150 must be transmitted bit−coded and without
a factor.