Troubleshooting and fault elimination

Fault messages
Causes and remedies

11

l

124

EDBCSXE040 EN 7.0

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

0070 U15

Undervoltage of external
low−voltage supply

Voltage

< 17 V

Check low−voltage supply

0071 CCr

System failure

Strong interference on control
cables

Control cables must be shielded

Ground or earth loops in wiring

PE wiring

0072 PR1

Checksum error in parameter
set 1

Contact Lenze

0079 PR5

Internal fault (EEPROM)

Contact Lenze

0095 FAN1

Fan monitoring (only for built−in
units ECSEE)

Heatsink fan

l

blocked

l

dirty

l

defective

Eliminate cause

0105 H05

Internal fault (memory)

Contact Lenze

0106 H06

Internal fault (power section)

During initialisation of the
power supply module a wrong
power stage has been detected

Contact Lenze

0260
1260
2260

NodeGuard Trp
NodeGuard Msg
NodeGuard Wrn

"Life Guarding Event"

The power supply module as
CAN slave does not receive a
node guarding telegram from
the CAN master within the
"Node Life Time".

l

Check wiring at X4.

l

Check CAN configuration

l

Make sure that "Node
Guarding" has been activated
in the CAN master.

l

Adapt "Node Life Time"
(C0382, C0383) to the setting
in the CAN master.

Advertising