Electrical installation

Drive system on the mains
Electrical isolation

5

l

38

EDBCSXE040 EN 7.0

5.2

Drive system on the mains

This information applies to the ECS drive system, consisting of:

ƒ

ECSxE... power supply module

ƒ

ECSxK series capacitor module (optional)

ƒ

ECSxS/P/M/A series axis module

ƒ

Motor

ƒ

Accessories

ƒ

Wiring

5.2.1

Electrical isolation

The integrated electrical isolation between the power section and the control section is a
protective separation (reinforced insulation) acc. to EN 61800−5−1.

To maintain this protective separation, it must be ensured that the external 24 V supply
and all components connected to this supply also have a protective separation (SELV/PELV)
acc. to EN 61800−5−1.

24 V supply

DC bus

X6/+24, GND

X22

Basic insulation (50 V)

Dig. input/output
X6/DI1, DI2, D24, DO1

Reinforced insulation
(300 V)

Thermostat

X6/T1, T2

CAN

X4

Mains

AIF

X21

X1

Fig. 5−1

Electrical isolation

Advertising