Configuring system bus (CAN)

Setting the boot−up time/cycle time

8

l

91

EDBCSXE040 EN 7.0

Parameter

C0356

Name

CAN time settings

Data type: INTEGER_32

Index: 24219

dec

= 5E9B

hex

Setting of the ...

l

Boot−up time

l

Cycle time

l

Activation delay

^ 90
Setting range

(min. value | unit | max. value)

0

ms

65000

Subcodes

Lenze setting

Information

C0356/1

3000 ms

CAN boot−up time

l

Delay time after mains connection for the
initialisation by the master.

l

Only valid if C0352 = 1 (master).

C0356/2

0 ms

Cycle time for CAN2_OUT

l

Diagnostics PDO C0390 (

^ 98)

C0356/3

0 ms

Cycle time for CAN3_OUT

l

Factor to task time for process data telegram
transmission.

l

0 ms = event−controlled data transmission (the
output data will only be transmitted if a value
changes in the output object)

C0356/4

20 ms

Delay time for initial transmission of the process data
object CAN3_OUT after the CAN bus changes to
"Operational"

Save changes with C0003 = 1.

The settings are only accepted after carrying out one of the following actions:

ƒ

Renewed switch−on of the 24 V low−voltage supply

ƒ

Reset node via the bus system (by the network management (NMT))

ƒ

Reset node with C0358 = 1

)

Note!

If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).