1 basic settings with gdc, Basic settings with gdc, Commissioning – Lenze ECSCExxx Power supply module User Manual

Page 62

Advertising
background image

Commissioning

Commissioning steps (overview)
Basic settings with GDC

6

l

62

EDBCSXE040 EN 7.0

6.1.1

Basic settings with GDC

)

Note!

Follow the commissioning steps in the given order!

Setting

Brief description

Detailed

information

Conditions

l

Mains is switched off. (Green LED is dark, red LED is
blinking)

l

Power supply module is inhibited.
– Control bit 1 (STE_RESET) = 0
– Power supply enable input X6/DI1 = LOW

l

For operation in an EtherCAT network:
– Plug EtherCAT communication module (EMF2192IB)

onto AIF interface (X1).

1.

Switch on low−voltage supply.

2.

XT keypad or
Connect PC/laptop (with
installed GDC parameter
setting program) to the
power supply module.

Parameter setting with XT keypad

l

Plug the XT keypad into the AIF interface (X1).

l

Not possible for operation in an EtherCAT network, since
the AIF interface (X1) is already assigned by the EtherCAT
module (see "Preconditions" above).

^ 76

Parameter setting with GDC

l

Connect PC/laptop to system bus interface (X4) with PC
system bus adapter EMF2173IB/EMF2177IB.

l

Start GDC and select the device to be set.

^ 74

3.

Set mains voltage.

Setting via C0173

l

Setting of the connected ECS axis modules:
– C0173: Set DC bus thresholds according to the mains

voltage used.

– Set C0175 = 3 (charging current limitation is not active)

^ 67

4.

Set function of the brake
resistor.

Setting via C0127
(Brake chopper and/or fast discharge function (short−circuit
braking))

^ 68

5.

Only for operation with
external brake resistor:
Deactivate monitoring of the
internal brake resistor.

C0579 = 3 (internal brake resistor deactivated)

^ 71

6.

Configure power supply
enable input.

l

DC bus is charged if X6/DI1 = HIGH

l

Set the response of the power supply module for
X6/DI1 = LOW via C0468.

^ 69

7.

Connect mains voltage.

The detection of the mains voltage takes about 1 second. If
the mains voltage is within the operating range (

^ 103)

l

the green LED at the power supply module will be
blinking.

l

XT keypad displays "ok".

8.

Select operating mode.

C0001 = 0

Operation via system bus (CAN) with master
control

^ 64

C0001 = 1

Control via digital inputs

^ 65

C0001 = 2

Operation via EtherCAT with master control

l

For this purpose, use the EtherCAT module
EMF2192IB.

^ 66