Advanced Program Group (continued)

A168 [PWM Frequency]

Related Parameter(s):

A169

Sets the carrier frequency for the PWM output waveform. The chart below provides derating
guidelines based on the PWM frequency setting.
Important: Ignoring derating guidelines can cause reduced drive performance.

Values

Default:

4.0 kHz

Min/Max:

2.0/10.0 kHz (Frame C and D drives)
2.0/8.0 kHz (Frame E, F, G and H drives)

Display:

0.1 kHz

% Output Curent (A)

68

84

88

80
76

96

100

92

72

64
60
56
52
50
48

Carrier Frequency (kHz)

8

7

6

5

4

3

2

1

10

9

A169 [PWM Mode]

Related Parameter(s):

A168

Selects the PWM algorithm used.

Options

0 “Space Vector”

3-Phase Modulation: Provides quiet operation and produces
less motor losses.

1 “2-Phase” (Default)

2-Phase Modulation: Provides less drive losses and best
performance with long motor cable runs.