T066, T068 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 77

Advertising
background image

Programming and Parameters

3-19

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

T065
Options
(Cont.)

16 “Logic In 1”

An input is programmed as “Logic In 1” and is active.

17 “Logic In 2”

An input is programmed as “Logic In 2” and is active.

24 “Fault” (with FRN 7.xx

and later)

Opto output is inactive when power is applied to the drive and
is active when a fault occurs. This is inverted from Option 0,
“Ready/Fault”.

T066 [Opto Out Level]

Related Parameter(s):

T065

,

T068

,

A163

,

d318

32 bit parameter.

Determines the on/off point for the opto output when

T065

[Opto Out Sel] is set to option 6, 7, 8, 9, 10

or 12.

Values

Default:

0.0

Min/Max:

0.0/9999

Display:

0.1

32

T065 Setting

T066 Min/Max

6
7
8
9
10
12

0/400 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1

T068 [Opto Out Logic]

Related Parameter(s):

T065

,

T066

Determines the logic (Normally Open/NO or Normally Closed/NC) of the opto output.

Note: Setting output to NC may cause output to “glitch” on power-up. The off/reset state of all outputs
is open.
Values

Default:

0

Min/Max:

0/1

Display:

1

T068 Option

Opto Out Logic

0
1

NO (Normally Open)
NC (Normally Closed)