3-22

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Terminal Block Group

(continued)

T074 [Analog In 2 Lo]

Related Parameter(s):

P034

,

P038

,

T072

,

T073

,

T075

T076

,

A152

,

A153

Stop drive before changing this parameter.

Sets the analog input level that corresponds to

P034

[Minimum Freq].

Analog inversion can be accomplished by setting this value larger than

T075

[Analog In 2 Hi].

Important: If analog inversion is implemented the drive will go to maximum frequency in the event the
analog input is lost. It is strongly recommended to activate

T072

[Analog In 1 Loss] to protect from this

potential occurrence.

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

0

P035 [Maximum Freq]

P034 [Minimum Freq]

T074 [Analog In 2 Lo]

T075 [Analog In 2 Hi]

0

Speed Reference

T075 [Analog In 2 Hi]

Related Parameter(s):

P035

,

P038

,

T073

,

T074

,

T076

A152

,

A153

Stop drive before changing this parameter.

Sets the analog input level that corresponds to P035 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than T074 [Analog In 2 Lo].

Values

Default:

100.0%

Min/Max:

0.0/100.0%

Display:

0.1%