Advanced Program Group (continued)
A210 [Wake PID Preload]
Related Parameter(s):
(with FRN 7.xx and later.)
Sets the value used to preload the PID integral component on wake. This value must be greater than
T078 [Sleep Level] or drive will not wake up.
Values
Default:
0.0 Hz (No preload)
Min/Max:
0.0/320.0 Hz
Display:
0.1 Hz
A210 [Wake PID Preload]
A210 = 0.0 Hz (no preload)
PID Output
Time
Wake
A157 [PID Setpoint]
A210 = 0.1 to 320.0 Hz