Advanced program group (continued), A210 [wake pid preload – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 112

Advertising
background image

3-54

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Advanced Program Group (continued)

A210 [Wake PID Preload]

Related Parameter(s):

T078

(with FRN 7.xx and later.)
Sets the value used to preload the PID integral component on wake. This value must be greater than
T078 [Sleep Level] or drive will not wake up.

Values

Default:

0.0 Hz (No preload)

Min/Max:

0.0/320.0 Hz

Display:

0.1 Hz

A210 [Wake PID Preload]

A210 = 0.0 Hz (no preload)

PID Output

Time

Wake

A157 [PID Setpoint]

A210 = 0.1 to 320.0 Hz