Programming and Parameters

3-17

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

T060
Options
(Cont.)

23 “Aux Motor”

Auxiliary Motor is commanded to run. Refer to

Appendix C

for

details.

24 “Fault” (with FRN 7.xx

and later)

Relay remains in the off state when power is applied to the
drive and energizes when a fault occurs. This is inverted from
Option 0, “Ready/Fault”.

T061 [Relay Out2 Level]

Related Parameter(s):

T060

,

T063

,

T064

,

d318

32 bit parameter.

Sets the trip point for the digital output relay if the value of

T060

[Relay Out2 Sel] is 6, 7, 8, 9, 10 or 12.

Values

Default:

0.0

Min/Max:

0.0/9999

Display:

0.1

32

T060 Setting

T061 Min/Max

6
7
8
9
10
12

0/320 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1

T063 [Relay 2 On Time]

Related Parameter(s):

T060

,

T061

,

T064

Sets delay time before Relay energizes after required condition testing.

Values

Default:

0.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

T064 [Relay 2 Off Time]

Related Parameter(s):

T060

,

T061

,

T063

Sets delay time before Relay de-energizes after required condition testing ceases.

Important: Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.

Values

Default:

0.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs