F-4

Metasys N2

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Table F.9 Binary Outputs

Network Point

Name

Description

Values

Type
(NPT)

Address
(NPA)

ON (“1”)

OFF (“0”)

BO

1

Run Enable

Logic Command bit 00

Enable

Stop (Coast)

BO

2

Start/Stop

Logic Command bit 00 & 01

Start

Stop (Normal)

BO

3

Jog

Logic Command bit 02

Jog

Not Jog

BO

4

Clear Faults

Logic Command bit 03

Clear Flts

Not Clear Flts

BO

5

Fwd/Rev

Logic Command bit 04 & 05

Forward

Reverse

BO

6

Not Used

Logic Command bit 06

BO

7

MOP Inc

Logic Command bit 07

Increment

Not Increment

BO

8

Accel 1

Logic Command bit 08

Accel Rate 1

Not Accel 1

BO

9

Accel 2

Logic Command bit 09

Accel Rate 2

Not Accel 2

BO

10

Decel 1

Logic Command bit 10

Decel Rate 1

Not Decel 1

BO

11

Decel 2

Logic Command bit 11

Decel Rate 2

Not Decel 2

BO

12

Ref Sel 1

Logic Command bit 12

BO

BO

13

Ref Sel 2

Logic Command bit 13

14

13

12

BO

14

Ref Sel 3

Logic Command bit 14

0

0

0

= No Command

0

0

1

= P038

[Speed

Reference]

0

1

0

= A142 [Internal Freq]

0

1

1

= Comm - Address 8193

(1)

1

0

0

= A143 [Preset Freq 0]

1

0

1

= A144 [Preset Freq 1]

1

1

0

= A145 [Preset Freq 2]

1

1

1

= A146 [Preset Freq 3]

BO

15

MOP Dec

Logic Command bit 15

Decrement

Not Decrement

BO

16

Pnl Lock

Lock-out Drive Front Panel

Lock

Unlock

BO

17

Digital Out 1

Relay #1 on Drive
(Drive Terminal R1, R2, R3)

On

Off

BO

18

Digital Out 2

Relay #2 on Drive
(Drive Terminal R4, R5, R6)

On

Off

BO

19

Opto Out

Terminal #19

On

Off

(1)

See Writing (06) Reference on

page E-3

.

Table F.10 Analog Outputs

Network Point

Name

Description

Units

Min/Max

Type
(NPT)

Address
(NPA)

AO

1

Reference

Reference

%

0/100

AO

2

Accel 1

P039 [Accel Time 1]

Secs

0.0/600.0

AO

3

Decel 1

P040 [Decel Time 1]

Secs

0.0/600.0

AO

4

Mtr OL Current P033 [Motor OL Current]

A

0.0/Rated

×

2

AO

5

PID Setpoint

A157 [PID Setpoint]

%

0/100

AO

6

Analog Out 1

Drive Analog Output #1 (T084)

%

AO

7

Analog Out 2

Drive Analog output #2 (T087)

%

AO

8

Write Param #

Param. number to write in AO 9

0 to Max Param.

AO

9

Write Value

Write value of param. selected by AO 8

Based on AO 8 selected param.

AO

10

Read Param #

Param. number to read in AI 9

0 to Max Param.

AO

11

User Out 1

User-defined Output 1
(Param. selected via ADI 5)

Varies by the parameter

selected.

AO

12

User Out 2

User-defined Output 2
(Param. selected via ADI 6)

AO

13

User Out 3

User-defined Output 3
(Param. selected via ADI 7)

AO

14

User Out 4

User-defined Output 4
(Param. selected via ADI 8)