Basic Program Group

(continued)

P036 [Start Source]

Related Parameter(s):

P037

,

P042

,

A166

,

d301

Stop drive before changing this parameter.

Sets the control scheme used to start the drive when in Auto/Remote mode.
Refer to

Start and Speed Reference Control on page 1-28

for details about how other drive settings

can override the setting of this parameter.
Important: For all settings except options 3 and 6, the drive must receive a leading edge from the
start input for the drive to start after a stop input, loss of power or fault condition.
Options

0 “Keypad”

Integral keypad controls drive operation.

I/O Terminal 01 = Stop: Coast to Stop

I/O Terminal 02 = Not Used

I/O Terminal 03 = Not Used

1 “3-Wire”

I/O Terminal Block controls drive operation.

I/O Terminal 01 = Stop: Per

P037

[Stop Mode]

I/O Terminal 02 = Start

I/O Terminal 03 = Direction

2 “2-Wire”

I/O Terminal Block controls drive operation.

I/O Terminal 01 = Stop: Coast to Stop

I/O Terminal 02 = Run FWD

I/O Terminal 03 = Run REV

3 “2-W Lvl Sens”

(Default)

I/O Terminal Block controls drive operation.

I/O Terminal 01 = Stop: Coast to Stop

I/O Terminal 02 = Run FWD

I/O Terminal 03 = Run REV

Drive will restart after a “Stop” command when:

Stop is removed and Run FWD is held active

4 “2-W Hi Speed”

I/O Terminal Block controls drive operation.

I/O Terminal 01 = Stop: Coast to Stop

I/O Terminal 02 = Run FWD

I/O Terminal 03 = Run REV

Outputs are kept in a ready-to-run state. The drive will
respond to a “Start” command within 10 ms.

Important: There is greater potential voltage on the output
terminals when using this option.

5 “Comm Port”

Remote communications controls drive operation.

I/O Terminal 01 = Stop: Coast to Stop

I/O Terminal 02 = Not Used

I/O Terminal 03 = Not Used

6 “2-W Lvl/Enbl”

I/O Terminal Block controls drive operation.

I/O Terminal 01 = Function Loss: Fault and Coast to Stop

I/O Terminal 02 = Run FWD

I/O Terminal 03 = SW Enable

Drive will restart after a “Stop” command when:

Stop is removed and Run FWD is held active

See Attention
Below

See Attention
Below

ATTENTION:

Hazard of injury exists due to unintended operation. When

P036 [Start Source] is set to option 3 or option 6, and the Run input is
maintained, the Run inputs do not need to be toggled after a Stop input or a
fault clear for the drive to run again. The drive will stop only when the stop
command is maintained or the drive is faulted.