Electrical

Voltage Tolerance:

200-240V ±10%
380-480V ±10%

Frequency Tolerance:

48-63 Hz

Input Phases:

Three-phase input provides full rating. Single-phase
operation provides 35% rated current.

Displacement Power Factor:

0.98 across entire speed range

Efficiency:

97.5% at rated amps, nominal line voltage

Maximum Short Circuit Rating:

100,000 Amps Symmetrical (Frame C Drives)
200,000 Amps Symmetrical (Frame D–H Drives)

Actual Short Circuit Rating:

Determined by AIC Rating of installed fuse/circuit
breaker

Transistor Type:

Isolated Gate Bipolar (IGBT)

Internal DC Bus Choke

200-240V AC Input:
380-480V AC Input:

11-37 kW (15-50 HP) Panel Mount Drives
18.5-160 kW (25-250 HP) Panel Mount Drives

Internal AC Line Reactor

380-480V AC Input:

200-250 kW (300-350 HP) Panel Mount Drives

Control

Method:

Sinusoidal PWM, Volts/Hertz

Carrier Frequency

Frames C and D:
Frames E – H:

2-10 kHz, Drive rating based on 4 kHz
2-8 kHz, Drive rating based on 4 kHz

Frequency Accuracy

Digital Input:
Analog Input:

Analog Output:

Within ±0.05% of set output frequency
Within 0.5% of maximum output frequency, 10-Bit
resolution
±2% of full scale, 10-Bit resolution

Speed Regulation - Open Loop with Slip
Compensation:

±1% of base speed across a 60:1 speed range

Output Frequency:

0-320 Hz (programmable)

Stop Modes:

Multiple programmable stop modes including - Ramp,
Coast, DC-Brake, Ramp-to-Hold and S Curve.

Accel/Decel:

Two independently programmable accel and decel
times. Each time may be programmed from 0 - 600
seconds in 0.1 second increments.

Drive Overload:

110% Overload capability for up to 1 minute

Electronic Motor Overload Protection

Provides class 10 motor overload protection according
to NEC article 430 and motor over-temperature
protection according to NEC article 430.126 (A) (2). UL
508C File 29572.

Control Inputs

Digital:

Quantity:

(3) Semi-programmable
(4) Programmable

Type

Source Mode (SRC):
Sink Mode (SNK):

18-24V = ON, 0-6V = OFF
0-6V = ON, 18-24V = OFF

Analog:

Quantity:

(1) Isolated, –10 to 10V or 4-20mA
(1) Non-isolated, 0 to 10V or 4-20mA

Specification

Resolution:
0 to 10V DC Analog:
4-20mA Analog:
External Pot:

10-bit
100k ohm input impedance
250 ohm input impedance
1-10k ohm, 2 Watt minimum