A166, Advanced program group (continued) – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 99

Advertising
background image

Programming and Parameters

3-41

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Advanced Program Group (continued)

A165 [Start At PowerUp]

Related Parameter(s):

P036

Stop drive before changing this parameter.

Enables/disables a feature that allows a Start or Run command to automatically cause the drive to
resume running at commanded speed after drive input power is restored. Requires a digital input
configured for Run or Start and a valid start contact.

This parameter will not function if parameter

P036

[Start Source] is set to 4 “2-W Hi Speed”.

Options

0 “Disabled” (Default)

1 “Enabled”

ATTENTION:

Equipment damage and/or personal injury may result if this parameter

is used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.

A166 [Reverse Disable]

Related Parameter(s):

b006

,

P036

,

T051

-

T054

Stop drive before changing this parameter.

Enables/disables the function that allows the direction of motor rotation to be changed. The reverse
command may come from a digital or a serial command. All reverse inputs including two-wire Run
Reverse will be ignored with reverse disabled.

Options

0 “Rev Enabled”

1 “Rev Disabled”

(Default)

A167 [Flying Start En]

Related Parameter(s):

A200

Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM.

Important: When this parameter is enabled, verify that A200 [Motor NP FLA] is set to the motor’s
actual full load amp value.

Options

0 “Disabled” (Default)

1 “Enabled”

Advertising