Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 203

Advertising
background image

Metasys N2

F-7

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Writing Parameter Values

These outputs are written each time the User OUTx point is written from
the network.

The Param# for OUTx’s default to commonly accessed parameters and
can be changed if desired. A value of “0” in the Param# for OUTx field
disables the writing of data for that specific point.

Figure F.2 Configurable Objects: Outputs

ATTENTION: Risk of equipment damage exists. If configurable
outputs are programmed to write parameter data to Non-Volatile
Storage (NVS) frequently, the NVS will quickly exceed its life cycle
and cause the drive to malfunction. Do not create a program that
frequently uses configurable outputs to write parameter data to NVS.

Table F.14 Configurable Objects: Outputs

Network Point

Description

Range

Default

Type
(NPT)

Address
(NPA)

AO

6

User OUT1

Varies by the parameter

selected by Param# for

OUTx.

0

AO

7

User OUT2

0

AO

8

User OUT3

0

AO

9

User OUT4

0

ADI

5

User OUT1 (A06)
Destination (Param#)

0 (not in use), 1 to
maximum # of drive
parameters

A154 [PID Prop Gain]

ADI

6

User OUT2 (A07)
Destination (Param#)

0 (not in use), 1 to
maximum # of drive
parameters

A155 [PID Integ Time]

ADI

7

User OUT3 (A08)
Destination (Param#)

0 (not in use), 1 to
maximum # of drive
parameters

A156 [PID Diff Rate]

ADI

8

User OUT4 (A09)
Destination (Param#)

0 (not in use), 1 to
maximum # of drive
parameters

A158 [PID Deadband]

Controller

Drive

Param#
for OUTx

User
OUTx

ADI

AO

Advertising