Installation/Wiring

1-25

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Analog Output
Unipolar, 4-20 mA Output

525 Ohm Maximum

DIP Switch

AO2 = 20MA

Parameters

T082 [Analog Out1 Sel] = 14 through 20

Scaling

T083 [Analog Out1 High]
T084 [Analog Out1 Setpt]

2 Wire Control
Sourcing (SRC),
Internal Supply,
Non-Reversing

Input must be active for the
drive to run.

When input is opened, the
drive will stop as specified by
P037 [Stop Mode].

Drive will not run if I/O
Terminal 01 is open. Drive will
coast to stop if opened while
running.

DIP Switch

SNK/SRC = SRC

Parameters

P036 [Start Source] = 2, 3, 4
P037 [Stop Mode] = 0 through 7

2 Wire Control
Sourcing (SRC),
External Supply,
Non-Reversing

Input must be active for the
drive to run.

When input is opened, the
drive will stop as specified by
P037 [Stop Mode].

User supplied 24V DC power
source must be used.

Each digital input draws 6 mA.

Drive will not run if I/O
Terminal 01 is open. Drive will
coast to stop if opened while
running.

DIP Switch

SNK/SRC = SRC

Parameters

P036 [Start Source] = 2, 3, 4
P037 [Stop Mode] = 0 through 7

2 Wire Control
Sinking (SNK),
Internal Supply,
Non-Reversing

Input must be active for the
drive to run.

When input is opened, the
drive will stop as specified by
P037 [Stop Mode].

Drive will not run if I/O
Terminal 01 is open. Drive will
coast to stop if opened while
running.

DIP Switch

SNK/SRC = SNK

Parameters

P036 [Start Source] = 2, 3, 4
P037 [Stop Mode] = 0 through 7

Input/Output

Connection Example

Required Settings

14

16

Common

+

11

01

02

Stop-Run

+24V

Common

01

02

04

Stop-Run

01

02

04

Stop-Run