22 installation/wiring – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 34

Advertising
background image

1-22

Installation/Wiring

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Table 1.H Control I/O Terminal Designations

No. Signal

Default

Description

Param.

01

Stop

(1)

/

Function Loss

Coast

Factory installed jumper or a normally closed input must
be present for the drive to start.
Program with P036 [Start Source].

P036

(1)

02

Start/Run FWD

HAND Mode: Command comes from Integral Keypad.
AUTO Mode: I/O Terminal 02 is active.
Program with P036 [Start Source].

P036

,

P037

03

Direction/Run REV

Rev Disabled

To enable reverse operation, program with A166
[Reverse Disable].
Program with P036 [Start Source].

P036

,

P037

,

A166

04

Digital Common

For digital inputs. Tied to I/O Terminal 09.
Electronically isolated with digital inputs from analog I/O
and opto output.

05

Digital Input 1

Purge

(2)

Program with T051 [Digital In1 Sel].

T051

06

Digital Input 2

Local

Program with T052 [Digital In2 Sel].

T052

07

Digital Input 3

Clear Fault

Program with T053 [Digital In3 Sel].

T053

08

Digital Input 4

Comm Port

Program with T054 [Digital In4 Sel].

T054

09

Digital Common

For digital inputs. Tied to I/O Terminal 04.
Electronically isolated with digital inputs from analog I/O
and opto output.

10

Opto Common

For opto-coupled outputs. Electronically isolated with
opto output from analog I/O and digital inputs.

11

+24V DC

Drive supplied power for digital inputs.
Referenced to Digital Common. Max. Output: 100mA.

12

+10V DC

Drive supplied power for 0-10V external potentiometer.
Referenced to Analog Common. Max. Output: 15mA.

P038

13

Analog Input 1

0-10V

External 0-10V (unipolar), 0-20mA or 4-20mA input
supply or potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI1 DIP Switch to 20mA.
Program with T069 [Analog In 1 Sel].
Input Impedance:

100k ohm (Voltage Mode)
250 ohm (Current Mode)

T069

,

T070

,

T071

,

T072

14

Analog Common 1

Common for Analog Input 1 and Analog Output 1 and 2.
Electrically isolated from digital I/O and opto output.

15

Analog Output 1

OutFreq 0-10

Default analog output is 0-10V.
For current (mA) value, set AO1 DIP Switch to 20mA.
Program with T082 [Analog Out1 Sel].
Maximum Load:

4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)

P038

,

T051

-

T054

,

A152

16

Analog Output 2

OutCurr 0-10

Default analog output is 0-10V.
For a current (mA) value, set AO2 DIP Switch to 20mA.
Program with T085 [Analog Out2 Sel].
Maximum Load:

4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)

T082

,

T084

,

T085

,

T086

,

T087

17

Analog Input 2

0-10V

Optically isolated external 0-10V (unipolar), ±10V
(bipolar), 0-20mA or 4-20mA input supply or
potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI2 DIP Switch to 20mA.
Program with T073 [Analog In 2 Sel].
Input Impedance: 100k ohm (Voltage Mode)

250 ohm (Current Mode)

T073

,

T074

,

T075

,

T076

18

Analog Common 2

For Analog Input 2. Electronically isolated from digital I/O
and opto output. With Analog Input 2, provides one fully
isolated analog input channel.

19

Opto Output

At Frequency

Program with T065 [Opto Out Sel].

T065

,

T066

,

T068

20

RS485 (DSI) Shield –

Terminal connected to Safety Ground - PE when using
the RS485 (DSI) Communication Port.

(1)

See Footnotes (1) and (4) on page

1-21

.

(2)

Important information regarding Stop commands and the [Digital Inx Sel] Purge option is provided on

page 3-12

.