A170, Advanced program group (continued), A170 [boost select – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 101

Advertising
background image

Programming and Parameters

3-43

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Advanced Program Group (continued)

A170 [Boost Select]

Related Parameter(s):

b004

,

P031

,

P032

,

A171

,

A172

,

A173

Sets the boost voltage (% of

P031

[Motor NP Volts]) and redefines the Volts per Hz curve.

Drive may add additional voltage unless Option 5 is selected.

Frames C-F

Frames G-H

Options

0 “Custom V/Hz”

0 “Custom V/Hz”

1 “30.0, VT”

1 “30.0, VT”

Typical Fan/Pump Curves

2 “35.0, VT”

2 “35.0, VT”

3 “40.0, VT”

3 “40.0, VT”

4 “45.0, VT” (Default)

4 “45.0, VT” (Default)

5 “0.0 no IR”

5 “0.0 no IR”

Boost Curves

6 “0.0”

6 “0.0”

7 “2.5”

7 “0.2”

8 “5.0”

8 “0.5”

9 “7.5”

9 “0.8”

10 “10.0”

10 “1.0”

11 “12.5”

11 “2.0”

12 “15.0”

12 “3.0”

13 “17.5”

13 “4.0”

14 “20.0”

14 “5.0”

15 “Kepco” Curve

(1)

15 “Kepco” Curve

(1)

(1)

Kepco Curve is used in specific systems to meet requirements of the Korean Electric Power
Company.

% P032 [Motor NP Hertz]

% P031 [Motor NP Volts]

100

50

1/2 [Motor NP Volts]

1/2

[Motor NP Hertz]

4
3
2
1

0

50

100

Settings

5-14

A174 [Maximum Voltage] can be set anywhere.
Settings greater than P031 [Motor NP Volts] define a point on the V/Hz curve.
Settings less than P031 [Motor NP Volts] function as limits only and do not change the V/Hz curve.

P034 [Minimum Freq] can be set anywhere.
Functions as a limit only and does not change the V/Hz curve.

P035 [Maximum Freq] can be set anywhere.
Settings greater than P032 [Motor NP Hertz]
define a point on the V/Hz curve.

P035 [Maximum Freq] can be set anywhere.
Settings less than P032 [Motor NP Hertz] function
as limits only and do not change the V/Hz curve.

Setting

Boost Voltage (% of Base)

5

0.0 (no IR Comp. added)

6 0.0
7 2.5
8 5.0
9 7.5
10 10.0
11 12.5
12 15.0
13 17.5
14 20.0
15 "Kepco"

Curve

(1)

Setting Fan/Pump

Curves

1 30.0
2 35.0
3 40.0
4 45.0

Advertising