Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 141

Advertising
background image

Troubleshooting

4-7

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Drive does not respond to changes in speed command.

Motor and/or drive will not accelerate to commanded speed.

Cause(s)

Indication

Corrective Action

No value is coming from the
source of the command.

The drive “Run” indicator is lit
and output is 0 Hz.

Check

d301

[Control Source] for

correct source.

If the source is an analog input,
check wiring and use a meter to
check for presence of signal.

Check

b002

[Commanded Freq]

to verify correct command.

Incorrect reference source is
being selected via remote
device or digital inputs.

None

Check

d301

[Control Source] for

correct source.

Check

d302

[Contrl In Status] to

see if inputs are selecting an
alternate source. Verify settings
for

T051

-

T054

[Digital Inx Sel].

Check

P038

[Speed Reference]

for the source of the speed
reference. Reprogram as
necessary.

Review the Speed Reference
Control chart on

page 1-28

.

Cause(s)

Indication

Corrective Action

Acceleration time is excessive. None

Reprogram

P039

[Accel Time 1] or

A147

[Accel Time 2].

Excess load or short
acceleration times force the
drive into current limit, slowing
or stopping acceleration.

None

Compare

b003

[Output Current] with

A179

[Current Limit 1].

Remove excess load or reprogram

P039

[Accel Time 1] or

A147

[Accel

Time 2].
Check for improper

A170

[Boost

Select] setting.

Speed command source or
value is not as expected.

None

Verify

b002

[Commanded Freq].

Check

d301

[Control Source] for the

proper Speed Command.

Programming is preventing the
drive output from exceeding
limiting values.

None

Check

P035

[Maximum Freq] to

insure that speed is not limited by
programming.

Advertising