Programming and Parameters
3-15
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
T055
Options
(Cont.)
23 “Aux Motor”
Auxiliary Motor is commanded to run. Refer to
for
details.
24 “Fault” (with FRN 7.xx
and later)
Relay remains in the off state when power is applied to the
drive and energizes when a fault occurs. This is inverted from
Option 0, “Ready/Fault”.
T056 [Relay Out1 Level]
Related Parameter(s):
,
,
,
32 bit parameter.
Sets the trip point for the digital output relay if the value of
[Relay Out1 Sel] is 6, 7, 8, 9, 10 or 12.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
32
T055 Setting
T056 Min/Max
6
7
8
9
10
12
0/320 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1
T058 [Relay 1 On Time]
Sets delay time before Relay energizes after required condition testing.
Values
Default:
0.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
T059 [Relay 1 Off Time]
Sets delay time before Relay de-energizes after required condition testing ceases.
Important: Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.
Values
Default:
0.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs