Advanced Program Group (continued)

A182 [Drive OL Mode]

Related Parameter(s):

P032

,

P033

Determines how the drive handles overload conditions that would otherwise cause the drive to fault.

Options

0 “DIsabled”

1 “Reduce CLim”

2 “Reduce PWM”

3 “Both-PWM 1st” (Default)

A183 [SW Current Trip]

Related Parameter(s):

P033

Enables/disables a software instantaneous (within 100 ms) current trip.

Values

Default:

0.0 (Disabled)

Min/Max:

0.0/(Drive Rated Amps

×

1.8)

Display:

0.1 Amps

A184 [Load Loss Level]

Related Parameter(s):

P033

Provides a software trip (Load Loss fault) when the current drops below this level for the time specified
in [Load Loss Time].

Values

Default:

0.0 (Disabled)

Min/Max:

0.0/Drive Rated Amps

Display:

0.1 Amps

A185 [Load Loss Time]

Related Parameter(s):

P033

Sets the required time for the current to be below [Load Loss Level] before a Load Loss fault occurs.

Values

Default:

0 Secs (Disabled)

Min/Max:

0/9999 Secs

Display:

1 Secs

A186 [Stall Fault Time]

Sets the time that the drive will remain in stall mode before a fault is issued.

Options

0 “60 Seconds” (Default)

1 “120 Seconds”

2 “240 Seconds”

3 “360 Seconds”

4 “480 Seconds”

5 “Flt Disabled”