Installation/Wiring

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Input Power Conditioning

The drive is suitable for direct connection to input power within the rated
voltage of the drive (see

Appendix A

). Listed in

Table 1.A

are certain

input power conditions which may cause component damage or
reduction in product life. If any of the conditions exist, as described in

Table 1.A

, install one of the devices listed under the heading Corrective

Action on the line side of the drive.

Important: Only one device per branch circuit is required. The device

should be mounted closest to the branch and sized to handle
the total current of the branch circuit.

Table 1.A Input Power Conditions

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line
reactance)

Install Line Reactor

(1)

or Isolation Transformer

(1)

Refer to

Appendix B

for accessory ordering information.

Line has power factor correction capacitors

Install Line Reactor

(1)

or Isolation Transformer

Line has frequent power interruptions

Line has intermittent noise spikes in excess of
6000V (lightning)

Phase to ground voltage exceeds 125% of
normal line to line voltage

Remove MOV jumper to ground
(Frame C, E and F drives only)

or Install Isolation Transformer with
grounded secondary if necessary

Ungrounded distribution system