Metasys N2 Data Types

Table F.1 Description of the Regions of a Virtual Object

Region

Type

Short Description

Region 1

Analog Input

AI

32-bit, IEEE-standard floats

Region 2

Binary Input

BI

1-bit

Region 3

Analog Output

AO

32-bit, IEEE-standard floats

Region 4

Binary Output

BO

1-bit

Region 5

Internal Float

ADF

32-bit, IEEE-standard floats (Analog Data Float)

Region 6

Internal Integer

ADI

16-bit (Analog Data Integer)

Region 7

Internal Byte

DB

8-bit (Analog Data Byte)

Table F.2 Internal Structure of Metasys N2 Analog Input (AI)

Attribute

Type

Description

1

Byte

Object Configuration

2

Byte

Object Status

3

Float

Analog Input Value

8

Float

Low Alarm Limit

9

Float

Low Warning Limit

10

Float

High Warning Limit

11

Float

High Alarm Limit

12

Float

Differential

Table F.3 Internal Structure of Metasys N2 Binary Input (BI)

Attribute

Type

Description

1

Byte

Object Configuration

2

Byte

Object Status

Table F.4 Internal Structure of Metasys N2 Analog Output (AO)

Attribute

Type

Description

1

Byte

Object Configuration

2

Byte

Object Status

3

Float

Current Value

Table F.5 Internal Structure of Metasys N2 Binary Output (BO)

Attribute

Type

Description

1

Byte

Object Configuration

2

Byte

Object Status

3

Integer

Minimum On-Time

4

Integer

Minimum Off-Time

5

Integer

Maximum Cycle/Hour

Table F.6 Internal Structure of Metasys N2 Internal Integer (ADI)

Attribute

Type

Description

1

Byte

Object Status

2

Integer

Current Value. Signed 16-bit.