F-6

Metasys N2

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Configurable objects are inputs and outputs that let you read and write
parameter values. These objects handle only 16-bit parameter values.

Reading Parameter Values

The configurable points may show any parameter in the drive by
configuring the Param# for INx point. The drive reads the value of the
parameter configured in the Param# for INx point and shows the result in
the User INx point. The Param# for INx’s default to commonly accessed
parameters and can be changed if desired. A “0” disables the fetching of
data and a “0” is returned in the respective User INx. See

Figure F.1

and

Table F.13

.

Figure F.1 Configurable Input Point Operation Objects Inputs

Using Metasys Configurable Objects to Access
Parameters

Table F.13 Configurable Objects: Inputs

Network Point

Name

Description

Default

Type
(NPT)

Address
(NPA)

AI

10

User IN1

User-defined Input 1

0

AI

11

User IN2

User-defined Input 2

0

AI

12

User IN3

User-defined Input 3

0

AI

13

User IN4

User-defined Input 4

0

ADI

1

Param# for IN1 User IN1 (AI 10)

Data Source (Param#)

b001 [Output Freq] (Hz)

ADI

2

Param# for IN2 User IN2 (AI 11)

Data Source (Param#)

b011 [Elapsed MWh]

ADI

3

Param# for IN3 User IN3 (AI 12)

Data Source (Param#)

b012 [Elapsed Run Time]

ADI

4

Param# for IN4 User IN4 (AI 13)

Data Source (Param#)

b014 [Drive Temp]

Controller

Drive

Param#
for INx

User
INx

Request

Response Data

ADI

AI