Example 2 one external motor with autoswap – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 190

Advertising
background image

D-14

Application Notes

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Example 2
One External Motor with AutoSwap

(1) Mechanically interlocked contactors are recommended to ensure that the

drive contactor and the line contactor do not close at the same time. If the
drive and line contactor close at the same time, drive damage may result.

Auxiliary Motor Control is enabled via Parameter

R239

[Aux Motor Mode].

Number of auxiliary motors is set via Parameter

R240

[Aux Motor Qty].

Relays are configured for Auxiliary Motor Control via parameters

T055

,

T060

,

R222

,

R225

,

R228

,

R231

,

R234

, and

R237

.

The frequency of Motor #1 that Motor #2 turns on at is set via Parameter

R241

[Aux 1 Start Freq].

The time that Motor #1 is above the value set by

R241

[Aux 1 Start Freq]

before turning on Motor #2 is set via Parameter

R250

[Aux Start Delay].

The frequency of Motor #1 that Motor #2 turns off at is set via Parameter

R242

[Aux 1 Stop Freq].

The time that Motor #1 is below the value set by

R242

[Aux 1 Stop Freq]

before turning off Motor #2 is set via Parameter

R251

[Aux Stop Delay].

The running time between the PowerFlex 400 switching control from Motor
#1 to Motor #2 is set via

R253

[Aux AutoSwap Time].

PID setup is done via Parameters

A150

through

A159

. See Appendix D for

additional information.

The maximum PID output level that an AutoSwap can occur is set via
Parameter

R254

[Aux AutoSwap Lvl]. AutoSwap will be delayed until the

PID output drops below this parameter setting.

Important: If using auxiliary motor control, ensure that wiring and parameter

configuration are correct before wiring contactor outputs. All relays
on the Auxiliary Relay Card will energize on power-up by default.
Failure to verify proper wiring and parameter configuration can result
in improper motor operation or drive damage.

PID

Reference

Feedback

Drive Relays

Auxiliary Relay Card

M1D

M1L

M2D

M2L

PowerFlex 400

Three-Phase Power

M1D

M1L

M2D

M2L

M1

M2

(1)

(1)