Basic Display Group
b001 [Output Freq]
Related Parameter(s):
Output frequency present at T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0.00/
[Maximum Freq]
Display:
0.01 Hz
b002 [Commanded Freq]
Related Parameter(s):
,
,
Value of the active frequency command. Displays the commanded frequency even if the drive is not
running.
Important: The frequency command can come from a number of sources. Refer to
Reference Control on page 1-28
for details.
Values
Default:
Read Only
Min/Max:
0.00/
[Maximum Freq]
Display:
0.01 Hz
b003 [Output Current]
The output current present at T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0.0/(Drive Rated Amps
×
2)
Display:
0.1 Amps
b004 [Output Voltage]
Related Parameter(s):
Output voltage present at terminals T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0/510
Display:
1 VAC
b005 [DC Bus Voltage]
Present DC bus voltage level.
Values
Default:
Read Only
Min/Max:
0/820
Display:
1 VDC