Programming and Parameters

3-53

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Advanced Program Group (continued)

A206 [ACT1 Minimum]

Related Parameter(s):

A204

(with FRN 7.xx and later.)
Sets the minimum value of the actual (ACT) 1 input. Used with the analog input min/max settings to
scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.

Values

Default:

0.0%

Min/Max:

0.0/200.0%

Display:

0.1%

A207 [ACT1 Maximum]

ACT1 %

Normal

A206 [ACT1 Minimum]

T070 [Analog In 1 Lo]

T071 [Analog In 1 Hi]

A206 [ACT1 Minimum]

ACT1 %

Inverted

A207 [ACT1 Maximum]

T070 [Analog In 1 Lo]

T071 [Analog In 1 Hi]

A207 [ACT1 Maximum]

Related Parameter(s):

A204

(with FRN 7.xx and later.)
Sets the maximum value of the actual (ACT) 1 input.

Values

Default:

100.0%

Min/Max:

0.0/200.0%

Display:

0.1%

A208 [ACT2 Minimum]

Related Parameter(s):

A205

(with FRN 7.xx and later.)
Sets the minimum value of the actual (ACT) 2 input. Used with the analog input min/max settings to
scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.

Values

Default:

0.0%

Min/Max:

0.0/200.0%

Display:

0.1%

A209 [ACT2 Maximum]

ACT2 %

Normal

A208 [ACT2 Minimum]

T074 [Analog In 2 Lo]

T075 [Analog In 2 Hi]

A208 [ACT2 Minimum]

ACT2 %

Inverted

A209 [ACT2 Maximum]

T074 [Analog In 2 Lo]

T075 [Analog In 2 Hi]

A209 [ACT2 Maximum]

Related Parameter(s):

A205

(with FRN 7.xx and later.)
Sets the maximum value of the actual (ACT) 2 input.

Values

Default:

100.0%

Min/Max:

0.0/200.0%

Display:

0.1%