Ungrounded Distribution Systems

Disconnecting MOVs (Drive Frames C, E and F only.)

To prevent drive damage, the MOVs connected to ground shall be
disconnected if the drive is installed on an ungrounded distribution
system where the line-to-ground voltages on any phase could exceed
125% of the nominal line-to-line voltage. To disconnect these devices,
remove the jumper shown in Figure

1.6

.

Figure 1.5 Phase to Ground MOV Removal

Figure 1.6 MOV Jumper Location

Note: Frame D, G and H drives do not contain a MOV to ground
connection and are suitable for operation in both grounded and
ungrounded distribution systems without modification.

AC Supply Source Considerations

ATTENTION: PowerFlex 400 drive frames contain protective MOVs
that are referenced to ground. These devices must be disconnected if the
drive is installed on an ungrounded or resistive grounded distribution
system.

R/L1
S/L2
T/L3

1

2

3

4

Three-Phase

AC Input

Jumper

Important:
Tighten screw after
jumper removal.

Frame C

Frame E and F (Typical)