T086, T087, Terminal block group – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 86: Continued)

Advertising
background image

3-28

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Terminal Block Group

(continued)

T086 [Analog Out2 High]

Related Parameter(s):

P035

,

T085

,

T087

Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.
Examples:

Values

Default:

100%

Min/Max:

0/800%

Display:

1%

T086 Setting

T085 Setting

T085 Max. Output Value

50%

1 “OutCurr 0-10”

5V for 200% Drive Rated Output Current

90%

11 “OutPowr 0-20”

18mA for 200% Drive Rated Power

T087 [Anlg Out2 Setpt]

Related Parameter(s):

T085

,

T086

Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog
output.

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

T088 [Anlg Loss Delay]

Related Parameter(s):

T069

,

T070

-

T076

Sets the length of time after power-up during which the drive will not detect an analog signal loss. The
drive response to an analog signal loss is set in

T072

or

T076

[Analog In x Loss].

Values

Default:

0.0 Secs

Min/Max:

0.0/20.0 Secs

Display:

0.1 Secs

T089 [Analog In Filter]

Sets level of additional filtering of the analog input signals. A higher number increases filtering and
decreases bandwidth. Each setting doubles the applied filtering (1 = 2x filter, 2 = 4x filter, etc.). No
additional filtering is applied when set to “0”.

Values

Default:

0

Min/Max:

0/14

Display:

1