Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 47

Advertising
background image

Installation/Wiring

1-35

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Figure 1.15 Connections and Grounding

(1) Shielded Enclosure required for 200-240V AC 11-22 kW (15-30 HP) PowerFlex 400

drives.

7.5 (10)

22C-D017N103

22-RF018-CS

10

No

11 (15)

22C-D022N103

22-RF026-CS

10

No

15 (20)

22C-D030N103

22-RFD036

100

No

18.5 (25)

22C-D038A103

22-RFD050

150

No

22 (30)

22C-D045A103

22-RFD050

150

No

30 (40)

22C-D060A103

22-RFD070

50

No

37 (50)

22C-D072A103

22-RFD100

50

No

45 (60)

22C-D088A103

22-RFD100

50

No

55 (75)

22C-D105A103

22-RFD150

150

No

75 (100)

22C-D142A103

22-RFD180

50

No

90 (125)

22C-D170A103

22-RFD208

50

No

110 (150)

22C-D208A103

22-RFD208

50

No

132 (200)

22C-D260A103

22-RFD323

50

Required

160 (250)

22C-D310A103

22-RFD480

50

Required

200 (300)

22C-D370A103

22-RFD480

50

Required

250 (350)

22C-D460A103

22-RFD480

50

Required

PowerFlex 400 Drive

Required Filter

Restrict Motor
Cable to (Meters)

Install Drive and
Filter in
Enclosure

kW (HP)

Cat. No.

R/L1

S/L2

T/L3

U/T1

V/T2

W/T3

EMI Fittings and Metal Conduit

IP 30/NEMA 1/UL Type 1
Option Kit (Frame C Drives Only)

Shielded Enclosure

(1)

Building Structure Steel

Enclosure Ground Connection

EMI Filter

L1'

L2'

L3'

L1

L2

L3

Shielded Motor Cable

Advertising