Advanced Display Group (continued)

d324 [Fault Frequency]

Related Parameter(s):

b001

Displays the value of

b001

[Output Freq] when the last fault occurred.

Values

Default:

Read Only

Min/Max:

0.00/320.00 Hz

Display:

0.01 Hz

d325 [Fault Current]

Related Parameter(s):

b003

Displays the value of

b003

[Output Current] when the last fault occurred.

Values

Default:

Read Only

Min/Max:

0.0/(Drive Rated Amps

×

2)

Display:

0.1 Amps

d326 [Fault Bus Volts]

Related Parameter(s):

b005

Displays the value of

b005

[DC Bus Voltage] when the last fault occurred.

Values

Default:

Read Only

Min/Max:

0/820 VDC

Display:

1 VDC

d327 [Status @ Fault]

Related Parameter(s):

b006

Displays the value of

b006

[Drive Status] when the last fault occurred.

Values

Default:

Read Only

Min/Max:

0/1

Display:

1

d328 [PID Fdbk Display]

Related Parameter(s):

b006

(With FRN 7.xx and later.)
Displays the active PID Feedback value.

Values

Default:

0.0%

Min/Max:

-200.0/200.0%

Display:

0.1%

d329 [DC Bus Ripple V]

Related Parameter(s):

b006

(With FRN 6.xx and later.)
Displays the real-time value of DC bus ripple voltage.
Excessive voltage ripple will eventually result in F017 Input Phase Loss fault.
Fault ripple levels are: 30V for 230V rated drives, and 60V for 460V rated drives.

Values

Default:

Read Only

Min/Max:

0/(410 for 230 VAC drives, 820 for 460 VAC drives) VDC

Display:

1 VDC