3-30

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

T091
Options
(Cont.)

6 “FB-SP>WakLvl”

PID Feedback Display minus PID Setpoint Display above
wake-up level.
If (d328 [PID Fdbk Display] - d304 [PID Setpnt Displ]) > T080
[Wake Level], then wake is enabled.

7 “SP-FB>WakLvl”

PID Setpoint Display minus PID Feedback Display above
wake-up level.
If (d304 [PID Setpnt Displ] - d328 [PID Fdbk Display]) > T080
[Wake Level], then wake is enabled.

8 “AI1 > WakDev”

Wake enabled from Analog Input 1 above PID Setpoint
Display plus wake deviation.
If d305 [Analog In 1] > (d304 [PID Setpnt Displ] + A203 [Wake
Deviation]), then wake is enabled.

9 “AI1 < WakDev”

Wake enabled from Analog Input 1 below PID Setpoint
Display minus wake deviation.
If d305 [Analog In 1] < (d304 [PID Setpnt Displ] - A203 [Wake
Deviation]), then wake is enabled.

10 “AI2 > WakDev”

Wake enabled from Analog Input 2 above PID Setpoint
Display plus wake deviation.
If d306 [Analog In 2] > (d304 [PID Setpnt Displ] + A203 [Wake
Deviation]), then wake is enabled.

11 “AI2 < WakDev”

Wake enabled from Analog Input 2 below PID Setpoint
Display minus wake deviation.
If d306 [Analog In 2] < (d304 [PID Setpnt Displ] - A203 [Wake
Deviation]), then wake is enabled.

12 “CFrq>WakDev”

Wake enabled based on drive command frequency above
PID Setpoint Display plus wake deviation.
If b002 [Commanded Freq] > (d304 [PID Setpnt Displ] - A203
[Wake Deviation]), then wake is enabled.

13 “CFrq<WakDev”

Wake enabled based on drive command frequency below PID
Setpoint Display minus wake deviation.
If b002 [Commanded Freq] < (d304 [PID Setpnt Displ] - A203
[Wake Deviation]), then wake is enabled.

T080 [Wake Level]

T080 [Wake Level]

T091 [Wake Sel]

= 6 “FB-SP>WakLvl”

PID Feedback

PID Setpoint

T091 [Wake Sel]

= 7 “SP-FB>WakLvl”