Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 55

Advertising
background image

Start Up

2-7

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Local/Remote Mode

In Local mode:

Start command and speed reference come from the integral keypad
Start/Hand and Digital Speed Increment and Decrement keys.

Auto key stops the drive and the drive switches to Remote mode.

Important: If the drive is running and P036 [Start Source] = 3 or 6

(2-Wire Control), the drive will continue to run at reference
defined by P038 [Speed Reference] if a valid start
command is present.

In Remote mode:

Auto key LED is illuminated.

Start command is defined by

P036

[Start Source].

Speed Reference command is defined by

P038

[Speed Reference].

Auto key stops the drive and the drive switches to Local mode.

Table 2.B P042 [Auto Mode]

=

2 “Local/Remote”

T051-T054 [Digital Inx Sel]

2 “Auto Mode” or 3 “Local”

Important: Certain digital input settings can override drive operation.

Refer to

Start and Speed Reference Control on page 1-28

for details.

Local Mode

Remote Mode

Key

LED Key Function

LED Key Function

On Starts drive.

Runs according to Speed Increment/
Decrement keys.

Off Not active.

Only active if P036 [Start Source] =
0 “Keypad”. Starts drive.

On Changes speed.

Off Not active.

Keys are only active if P038 [Speed
Source] = 0 “Drive Pot”.

Off Stops drive and changes to Remote

Mode.

On Stops drive and changes to Local

Mode.

N/A Stops drive.

N/A Stops drive.