Network wiring consists of a shielded 2-conductor cable that is
daisy-chained from node to node.

Figure 1.12 Network Wiring Diagram

Only pins 4 and 5 on the RJ45 plug should be wired. The other pins on
the PowerFlex 400 RJ45 socket contain power, etc. for other Rockwell
Automation peripheral devices and must not be connected.

Wiring terminations on the master controller will vary depending on the
master controller used and “TxRxD+” and “TxRxD-” are shown for
illustration purposes only. Refer to the master controller’s user manual
for network terminations. Note that there is no standard for the “+” and
“-” wires, and consequently Modbus device manufacturers interpret
them differently. If you have problems with initially establishing
communications, try swapping the two network wires at the master
controller.

On Drive Connections

PowerFlex 400 Frame D, E, F, G and H drives are equipped with two
RS485 (DSI) ports. One is accessible via an access door when the cover
is on and one is only accessible with the cover off. When one of these
ports has a Rockwell DSI device connected, the second port cannot be
used.

Figure 1.13 Frame D, E, F, G and H RS485 Ports

RS485 Network Wiring

Master

PowerFlex 400

Node 1

4

5

PowerFlex 400

Node 2

4

5

PowerFlex 400

Node "n"

4

5

TxRxD+

TxRxD-

TxRxD+

TxRxD-

TxRxD+

TxRxD-

NOTE: The shield should be grounded at ONLY ONE location.

Shield

Shield

Shield

120 ohm resistor

120 ohm resistor

FRONT

PIN 8

PIN 1

RS485 (DSI) Network Connection

Second RS485 (DSI) Connection