Application Notes

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

PID Preload

The value set in

A159

[PID Preload], in Hertz, will be pre-loaded into

the integral component of the PID at any start or enable. This will cause
the drive’s frequency command to initially jump to that preload
frequency, and the PID loop starts regulating from there.

PID Limits

A150

[PID Trim Hi] and

A151

[PID Trim Lo] are used to limit the PID

output and are only used in trim mode. [PID Trim Hi] sets the maximum
frequency for the PID output in trim mode. [PID Trim Lo] sets the
reverse frequency limit for the PID output in trim mode. Note that when
the PID reaches the Hi or Lo limit, the PID regulator stops integrating so
that windup does not occur.

PID Enabled

Freq Cmd

PID Output

PID Pre-load Value

PID Pre-load Value > 0