Supplemental drive information a-3 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 145

Advertising
background image

Supplemental Drive Information

A-3

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Category

Specification

Agency
Certification

Listed to UL508C and CAN/CSA-22.2
Listed to UL508C for plenums

Certified to AS/NZS, 1997 Group 1, Class A

Marked for all applicable European Directives
EMC Directive (89/336)

EN 61800-3, EN 50081-1, EN 50082-2

Low Voltage Directive (73/23/EEC)

EN 50178, EN 60204

The drive is also designed to meet the appropriate portions of the following specifications:

NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and

Operation of Adjustable Speed Drive Systems.

IEC 146 - International Electrical Code.

Protection

Bus Overvoltage Trip:

200-240V AC Input: 405V DC bus voltage (equivalent
to 290V AC incoming line)
380-460V AC Input: 810V DC bus voltage (equivalent
to 575V AC incoming line)

Bus Undervoltage Trip:

200-240V AC Input: 210V DC bus voltage (equivalent
to 150V AC incoming line)
380-480V AC Input: 390V DC bus voltage (equivalent
to 275V AC incoming line)

Power Ride-Thru:

100 milliseconds

Logic Control Ride-Thru:

0.5 seconds minimum, 2 seconds typical

Electronic Motor Overload Protection:

Provides class 10 motor overload protection according
to NEC article 430 and motor over-temperature
protection according to NEC article 430.126 (A) (2). UL
508C File 29572.

Overcurrent:

180% hardware limit, 220% instantaneous fault

Ground Fault Trip:

Phase-to-ground on drive output

Short Circuit Trip:

Phase-to-phase on drive output

Environment

Altitude:

1000 m (3300 ft) max. without derating.
Above 1000 m (3300 ft), derate 1% for every 100 m
(328 ft) up to a maximum altitude of 2000 m (6600 ft).

Maximum Surrounding Air Temperature
without derating:

IP20, Open Type:
IP30, NEMA Type 1, UL Type 1:

–10 to 50 degrees C (14 to 122 degrees F)
–10 to 45 degrees C (14 to 113 degrees F)

Cooling Method:

Fan: All drive ratings

Storage Temperature:

2.2 kW (3.0 HP) to 7.5 kW (10 HP)
11 kW (15 HP) to 250 kW (350 (HP)

–40 to 85 degrees C (–40 to 185 degrees F)
–40 to 70 degrees C (–40 to 158 degrees F)

Atmosphere:

Important: Drive must not be installed in an area
where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going to
be installed for a period of time, it must be stored in an
area where it will not be exposed to a corrosive
atmosphere.

Relative Humidity:

0 to 95% non-condensing

Shock (operating):

15G peak for 11 ms duration (

±

1.0 ms)

Vibration (operating):

1G peak, 5 to 2000 Hz

Seismic Rating

Meets the seismic requirements of the 2003
International Building Code as specified by AC156.

(1)

(1)

Drives 75 kW (100 HP) and greater have not been tested.