Essential requirements for ce compliance, 32 installation/wiring – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 44

Advertising
background image

1-32

Installation/Wiring

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Essential Requirements for CE Compliance

Conditions 1-4 listed below must be satisfied for PowerFlex drives to
meet the requirements of EN61800-3.

1. Grounding as described in

Figure 1.14

. Refer to

page 1-12

for

additional grounding recommendations.

2. Output power, control (I/O) and signal wiring must be braided,

shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.

3. All shielded cables should terminate with the proper shield

connector.

4. Conditions in

Table 1.K

.

Table 1.K PowerFlex 400 – EN61800-3 Compliance

PowerFlex 400 Drive

First Environment Restricted

First Environment Unrestricted

kW (HP)

Cat. No.
22C-…

Required Filter
(Allen-Bradley)

Restrict
Motor
Cable to
(Meters)

Install Drive
and Filter in
Shielded
Enclosure

Required Filter

Restrict
Motor
Cable to
(Meters)

Install Drive
and Filter in
Shielded
Enclosure

200-240 Volts

2.2 (3.0)

B012N103

22-RF034-CS

10

No

22-RF034-CS

1

Required

3.7 (5.0)

B017N103

22-RF034-CS

10

No

22-RF034-CS

1

Required

5.5 (7.5)

B024N103

22-RF034-CS

10

No

22-RF034-CS

1

Required

7.5 (10)

B033N103

22-RF034-CS

10

No

22-RF034-CS

1

Required

11 (15)

B049A103

22-RFD070

150

Required

Deltron MIF Series

50

Required

15 (20)

B065A103

22-RFD100

150

Required

Deltron MIF Series

50

Required

18.5 (25)

B075A103

22-RFD100

150

Required

Deltron MIF Series

50

Required

22 (30)

B090A103

22-RFD150

150

Required

Deltron MIF Series

50

Required

30 (40)

B120A103

22-RFD150

150

No

Deltron MIF Series

50

Required

37 (50)

B145A103

22-RFD180

150

No

Deltron MIF Series

75

Required

380-480 Volts

2.2 (3.0)

D6P0N103

22-RF018-CS

10

No

22-RF018-CS

1

Required

4.0 (5.0)

D010N103

22-RF018-CS

10

No

22-RF018-CS

1

Required

5.5 (7.5)

D012N103

22-RF018-CS

10

No

22-RF018-CS

1

Required

7.5 (10)

D017N103

22-RF018-CS

10

No

22-RF018-CS

1

Required

11 (15)

D022N103

22-RF026-CS

10

No

22-RF026-CS

1

Required

15 (20)

D030N103

22-RFD036

100

No

Deltron MIF Series

5

Required

18.5 (25)

D038A103

22-RFD050

150

No

Deltron MIF Series

5

Required

22 (30)

D045A103

22-RFD050

150

No

Deltron MIF Series

5

Required

30 (40)

D060A103

22-RFD070

50

No

Deltron MIF Series

5

Required

37 (50)

D072A103

22-RFD100

50

No

Deltron MIF Series

5

Required

45 (60)

D088A103

22-RFD100

50

No

Deltron MIF Series

5

Required

55 (75)

D105A103

22-RFD150

150

No

Deltron MIF Series

5

Required

75 (100)

D142A103

22-RFD180

50

No

Deltron MIF Series

5

Required

90 (125)

D170A103

22-RFD208

50

No

22-RFD208

5

Required

110 (150) D208A103

22-RFD208

50

No

22-RFD208

5

Required

132 (200) D260A103

22-RFD323

50

Required

22-RFD323

5

Required

160 (250) D310A103

22-RFD480

50

Required

22-RFD480

5

Required

200 (300) D370A103

22-RFD480

50

Required

22-RFD480

5

Required

250 (350) D460A103

22-RFD480

50

Required

22-RFD480

5

Required

Advertising