A178 [DC Brk Time@Strt]

Related Parameter(s):

P037

,

A177

Sets the length of time that DC brake current is “injected” into the motor after a valid start command is
received. Parameter

A177

[DC Brake Level] controls the level of braking current used.

Values

Default:

0.0 Secs

Min/Max:

0.0/99.9 Secs (A setting of 99.9 = Continuous)

Display:

0.1 Secs

Volts/Speed

Time

Start Command

[DC Brake Level]

[DC Brk Time@Strt]

Voltage

Speed

A179 [Current Limit 1]

Related Parameter(s):

P033

Maximum output current allowed before current limiting occurs.

Values

Default:

Drive Rated Amps

×

1.1

Min/Max:

0.0/(Drive Rated Amps

×

1.5)

Display:

0.1 Amps

A180 [Current Limit 2]

Related Parameter(s):

P033

Maximum output current allowed before current limiting occurs.

Values

Default:

Drive Rated Amps

×

1.1

Min/Max:

0.0/(Drive Rated Amps

×

1.5)

Display:

0.1 Amps

A181 [Motor OL Select]

Related Parameter(s):

P032

,

P033

,

P043

Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I

2

t

overload function.

Options

0 “No Derate” (Default)

1 “Min Derate”

2 “Max Derate”

Min Derate

0

80

100

60

40

20

No Derate

0

80

100

60

40

20

%

of P033

[Motor OL Curent

]

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25