Motor operation is unstable.
Drive will not reverse motor direction.
Drive does not power up.
Cause(s)
Indication
Corrective Action
Motor data was incorrectly
entered.
None
1. Correctly enter motor nameplate
,
.
2. Enable
[Compensation].
3. Use
[Boost Select] to
reduce boost level.
Cause(s)
Indication
Corrective Action
Digital input is not selected for
reversing control.
None
Check
[Digital Inx Sel]
[Start Source]. Choose
correct input and program for
reversing mode.
Digital input is incorrectly
wired.
None
Check input wiring.
Motor wiring is improperly
phased for reverse.
None
Switch two motor leads.
Reverse is disabled.
None
Check
[Reverse Disable].
Cause(s)
Indication
Corrective Action
No input power to drive.
None
Check the power circuit.
•
Check the supply voltage.
•
Check all fuses and disconnects.
Jumper between Power
Terminals P2 and P1 not
installed and/or DC Bus
Inductor not connected.
None
Install jumper or connect DC Bus
Inductor.