D-6

Application Notes

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Analog PID Reference Signals

Parameters

T070

[Analog In 1 Lo],

T071

[Analog In 1 Hi],

T074

[Analog In 2 Lo], and

T075

[Analog In 2 Hi] are used to scale or invert

an analog PID Reference.

Examples

Scale Function

For a 0-5 volt signal, the following parameter settings are used so that a 0
volt signal = 0% PID Reference and a 5 volt signal = 100% PID
Reference.

T069

[Analog In 1 Sel] or

T073

[Analog In 2 Sel] = 2 “Voltage Mode

- Unipolar”.

T070

[Analog In 1 Lo] or

T074

[Analog In 2 Lo] = 0.0%

T071

[Analog In 1 Hi] or

T075

[Analog In 2 Hi] = 50.0%

A152

[PID Ref Sel] = 0 “0-10V Input”

5 “ACT1 * ACT2”

Selects actual inputs

A204

[ACT1 Input] multiplied by

A205

[ACT2 Input] to be used as the feedback signal.

6 “ACT1 / ACT2”

Selects actual inputs

A204

[ACT1 Input] divided by

A205

[ACT2 Input] to be used as the feedback signal.

7 “Min A1, A2”

Selects the smaller of actual inputs

A204

[ACT1 Input] or

A205

[ACT2 Input] to be used as the feedback signal.

8 “Max A1, A2”

Selects the larger of actual inputs

A204

[ACT1 Input] or

A205

[ACT2 Input] to be used as the feedback signal.

Option

Description

0 10 20 30 40 50 60 70 80 90 100

PID Reference (%)

Input V

olts

2

4

6

8

10

12