Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 186

Advertising
background image

D-10

Application Notes

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Guidelines for Adjusting the PID Gains

1. Adjust the proportional gain. During this step it may be desirable to

disable the integral gain and differential gain by setting them to 0.
After a step change in the PID Feedback:

If the response is too slow increase

A154

[PID Prop Gain].

If the response is too quick and/or unstable (see

Figure D.1

),

decrease

A154

[PID Prop Gain].

Typically,

A154

[PID Prop Gain] is set to some value below the

point where the PID begins to go unstable.

2. Adjust the integral gain (leave the proportional gain set as in Step 1).

After a step change in the PID Feedback:

If the response is too slow (see

Figure D.2

), or the PID Feedback

does not become equal to the PID Reference, decrease

A155

[PID Integ Time].

If there is a lot of oscillation in the PID Feedback before settling
out (see

Figure D.3

), increase

A155

[PID Integ Time].

3. At this point, the differential gain may not be needed. However, if

after determining the values for

A154

[PID Prop Gain] and

A155

[PID Integ Time]:

Response is still slow after a step change, increase

A156

[PID

Diff Rate].

Response is still unstable, decrease

A156

[PID Diff Rate].

Advertising