A147, A148, Advanced program group (continued) – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 94: A147 [accel time 2, A148 [decel time 2

Advertising
background image

3-36

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Advanced Program Group (continued)

A147 [Accel Time 2]

Related Parameter(s):

P039

,

T051

-

T054

,

A143

-

A146

When active, sets the rate of acceleration for all speed increases. Refer to the flowchart on page

1-29

for details.

Values

Default:

30.00 Secs

Min/Max:

0.00/600.00 Secs

Display:

0.01 Secs

Maximum Freq

Accel Time

Accel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039 or A147

[Accel Time x]

P040 or A148

[Decel Time x]

0

Acceleratio

n

Deceleration

A148 [Decel Time 2]

Related Parameter(s):

P040

,

T051

-

T054

,

A143

-

A146

When active, sets the rate of deceleration for all speed decreases. Refer to the flowchart on page

1-29

for details.

Values

Default:

30.00 Secs

Min/Max:

0.01/600.00 Secs

Display:

0.01 Secs

Maximum Freq

Decel Time

Decel Rate

=

Advertising