Terminal Block Group

(continued)

T082 [Analog Out1 Sel]

Related Parameter(s):

P035

,

T083

,

T084

Sets the analog output signal mode (0-20 mA, 4-20 mA, or 0-10V). The output is used to provide a
signal that is proportional to several drive conditions. This parameter must match DIP Switch AO1
setting.

Setting

Output
Range

Min. Output
Value

Max. Output Value =
[Analog Output Hi]

Filter

(1)

DIP Switch
AO1
Setting

Related
Parameter

0

OutFreq 0-10 0-10V

0V = 0 Hz

[Maximum Freq]

None

10V

b001

1

OutCurr 0-10 0-10V

0V = 0 Amps

200% Drive Rated FLA

Filter A

10V

b003

2

OutTorq 0-10 0-10V

0V = 0 Amps

200% Drive Rated FLA

Filter A

10V

b013

3

OutVolt 0-10

0-10V

0V = 0 Volts

120% Drive Rated Output V None

10V

b004

4

OutPowr 0-10 0-10V

0V = 0 kW

200% Drive Rated Power

Filter A

10V

b010

5

Setpnt 0-10

0-10V

0V = 0.0%

100.0% Setting

None

10V

T084

6

TstData 0-10

0-10V

0V = 0000

65535 (Hex FFFF)

None

10V

A196

7

OutFreq 0-20 0-20 mA 0 mA = 0 Hz

[Maximum Freq]

None

20 mA

b001

8

OutCurr 0-20 0-20 mA 0 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b003

9

OutTorq 0-20 0-20 mA 0 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b013

10 OutVolt 0-20

0-20 mA 0 mA = 0 Volts

120% Drive Rated Output V None

20 mA

b004

11 OutPowr 0-20 0-20 mA 0 mA = 0 kW

200% Drive Rated Power

Filter A

20 mA

b010

12 Setpnt 0-20

0-20 mA 0 mA = 0.0%

100.0% Setting

None

20 mA

T084

13 TstData 0-20

0-20 mA 0 mA = 0000

65535 (Hex FFFF)

None

20 mA

A196

14 OutFreq 4-20 4-20 mA 4 mA = 0 Hz

[Maximum Freq]

None

20 mA

b001

15 OutCurr 4-20 4-20 mA 4 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b003

16 OutTorq 4-20 4-20 mA 4 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b013

17 OutVolt 4-20

4-20 mA 4 mA = 0 Volts

120% Drive Rated Output V None

20 mA

b004

18 OutPowr 4-20 4-20 mA 4 mA = 0 kW

200% Drive Rated Power

Filter A

20 mA

b010

19 Setpnt 4-20

4-20 mA 4 mA = 0.0%

100.0% Setting

None

20 mA

T084

20 TstData 4-20

4-20 mA 4 mA = 0000

65535 (Hex FFFF)

None

20 mA

A196

21 MinFreq 0-10 0-10V

0V = Min. Freq

[Maximum Freq]

None

10V

b001

22 MinFreq 0-20 0-20 mA 0 mA = Min. Freq

[Maximum Freq]

None

20 mA

b001

23 MinFreq 4-20 4-20 mA 4 mA = Min. Freq

[Maximum Freq]

None

20 mA

b001

24 AnlgIn1 0-10

0-10V

0V = 0.0%

100.0% Setting

Filter A

10V

d305

25 AnlgIn1 0-20

0-20 mA 0 mA = 0.0%

100.0% Setting

Filter A

20 mA

d305

26 AnlgIn1 4-20

4-20 mA 4 mA = 0.0%

100.0% Setting

Filter A

20 mA

d305

27 AnlgIn2 0-10

0-10V

0V = 0.0%

100.0% Setting

Filter A

10V

d306

28 AnlgIn2 0-20

0-20 mA 0 mA = 0.0%

100.0% Setting

Filter A

20 mA

d306

29 AnlgIn2 4-20

4-20 mA 4 mA = 0.0%

100.0% Setting

Filter A

20 mA

d306

(1)

For settings with the filter enabled, if a 0-100% step change occurs, the output will reach 95% in
500 milliseconds, 99% in 810 milliseconds and 100% in 910 milliseconds.

Values

Default:

0

Min/Max:

0/29

Display:

1