3-18

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Terminal Block Group

(continued)

T065 [Opto Out Sel]

Related Parameter(s):

P033

,

T066

,

T068

,

T072

T076

,

A163

,

d318

Determines the operation of the programmable opto output.
Options

0 “Ready/Fault”

Opto output is active when power is applied. This indicates
that the drive is ready for operation. Opto output is inactive
when power is removed or a fault occurs.

1 “At Frequency”

(Default)

Drive reaches commanded frequency.

2 “MotorRunning”

Motor is receiving power from the drive.

3 “Hand Active”

Active when drive is in local control.

4 “Motor Overld”

Motor overload condition exists.

5 “Ramp Reg”

Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.

6 “Above Freq”

Drive exceeds the frequency (Hz) value set in

T066

[Opto

Out Level].

Use T066 to set threshold.

7 “Above Cur”

Drive exceeds the current (% Amps) value set in

T066

[Opto Out Level].

Use T066 to set threshold.

Important: Value for

T066

[Opto Out Level] must be entered

in percent of drive rated output current.

8 “Above DCVolt”

Drive exceeds the DC bus voltage value set in

T066

[Opto

Out Level].

Use T066 to set threshold.

9 “Above Anlg 2”

Analog input voltage (I/O Terminal 17) exceeds the value
set in

T066

[Opto Out Level].

Do not use if

T073

[Analog In 2 Sel] is set to 3 “Voltage

Mode - Bipolar”.

This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 17) is wired to a
PTC and external resistor.

Use T066 to set threshold.

10 “Above PF Ang”

Power Factor angle has exceeded the value set in

T066

[Opto Out Level].

Use T066 to set threshold.

11 “Anlg In Loss”

Analog input loss has occurred. Program

T072

[Analog In 1

Loss] and/or

T076

[Analog In 2 Loss] for desired action when

input loss occurs.

12 “ParamControl”

Enables the output to be controlled over network
communications by writing to

T066

[Opto Out Level].

(0 = Off, 1 = On.)

13 “Retries Exst”

Value set in

A163

[Auto Rstrt Tries] is exceeded.

14 “NonRec Fault”

Number of retries for

A163

[Auto Rstrt Tries] is exceeded

OR

Non-resettable fault occurs OR

A163

[Auto Rstrt Tries] is not enabled.

15 “Reverse”

Drive is commanded to run in reverse direction.