Advanced program group (continued) – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 97

Advertising
background image

Programming and Parameters

3-39

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual

Publication 22C-UM001I-EN-P

Advanced Program Group (continued)

A154 [PID Prop Gain]

Sets the value for the PID proportional component when the PID mode is enabled by A152 [PID Ref
Sel].

Values

Default:

1.00

Min/Max:

0.00/99.99

Display:

0.01

A155 [PID Integ Time]

Sets the value for the PID integral component when the PID mode is enabled by A152 [PID Ref Sel].

Values

Default:

2.0 Secs

Min/Max:

0.0/999.9 Secs

Display:

0.1 Secs

A156 [PID Diff Rate]

Sets the value for the PID differential component when the PID mode is enabled by A152 [PID Ref
Sel].

Values

Default:

0.00 (1/Secs)

Min/Max:

0.00/99.99 (1/Secs)

Display:

0.01 (1/Secs)

A157 [PID Setpoint]

Provides an internal fixed value for process setpoint when the PID mode is enabled by A152 [PID Ref
Sel].

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

A158 [PID Deadband]

Sets the lower limit of the PID output.

Values

Default:

0.0%

Min/Max:

0.0/10.0%

Display:

0.1%

A159 [PID Preload]

Sets the value used to preload the integral component on start or enable.

Values

Default:

0.0 Hz

Min/Max:

0.0/320.0 Hz

Display:

0.1 Hz