T078, T079, T080 – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual

Page 82: T081, Terminal block group, Continued)

Advertising
background image

3-24

Programming and Parameters

PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P

Terminal Block Group

(continued)

T078 [Sleep Level]

Related Parameter(s):

T077

,

T079

,

T080

,

T081

Sets the analog input level the drive must reach to enter sleep mode.

Values

Default:

10.0%

Min/Max:

0.0/100.0%

Display:

0.1%

T079 [Sleep Time]

Related Parameter(s):

T077

,

T078

,

T080

,

T081

Sets the analog input time the drive must stay below to enter sleep mode.

Values

Default:

0.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

T080 [Wake Level]

Related Parameter(s):

T077

,

T078

,

T079

,

T081

Sets the analog input level the drive must reach to wake from sleep mode.

Values

Default:

15.0%

Min/Max:

0.0/100.0%

Display:

0.1%

T081 [Wake Time]

Related Parameter(s):

T077

,

T078

,

T079

,

T080

Sets the analog input time the drive must stay above to wake from sleep mode.

Values

Default:

0.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs