Figure 1.1, Figure 1.2, Minimum mounting clearances – Rockwell Automation 22C PowerFlex 400 AC Drive FRN 1.xx - 7.xx User Manual
Page 18
Advertising
![background image](/manuals/577083/18/background.png)
1-6
Installation/Wiring
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Minimum Mounting Clearances
Refer to
for mounting dimensions.
Figure 1.1 Frame C Mounting Clearances
Figure 1.2 Frames D & E Mounting Clearances
120 mm
(4.7 in.)
120 mm
(4.7 in.)
25 mm
(1.0 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
Closest object that
may restrict air flow
through the drive heat
sink and chassis.
Mounting Option A
No clearance required
between drives.
Mounting Option B
150 mm
(6.0 in.)
150 mm
(6.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)